Passive:Verification: Unterschied zwischen den Versionen

Aus Wufiwiki
Zur Navigation springenZur Suche springen
Keine Bearbeitungszusammenfassung
Keine Bearbeitungszusammenfassung
Zeile 47: Zeile 47:
== Annual Heat/Cooling Demand ==
== Annual Heat/Cooling Demand ==
[[Bild:Passive-verification_heatcooling_demand.png|right|thumb|Heat/Cooling demand]]
[[Bild:Passive-verification_heatcooling_demand.png|right|thumb|Heat/Cooling demand]]
Opposes annual heat gains and losses and thereby calculates the annual heat/cooling demand.<br>
This displays the balance between annual heat gains and losses and thereby calculates the annual heat/cooling demand.<br>
The losses/gains are summarized by categories and grphically displayed on bottom for better review.<br>
The losses/gains are summarized by categories and their balance is graphically displayed on the bottom. <br>
Note: the heat gains during heating period and the heat losses during the cooling period are reduced by the Utilization Factor. The Utilization Factor is estimated by a complex calculation.
Note: the heat gains during heating period and the heat losses during the cooling period are reduced by the Utilization Factor. The Utilization Factor is estimated by a complex calculation.
<br style="clear:both" />
<br style="clear:both" />
Zeile 54: Zeile 54:
== Heating/Cooling Load ==
== Heating/Cooling Load ==
[[Bild:Passive-verification_heatcooling_load.png|right|thumb|Heat/Cooling load]]
[[Bild:Passive-verification_heatcooling_load.png|right|thumb|Heat/Cooling load]]
Apart from the Utilization Factor, the calculation is similar to the heating/cooling demand calculation. The results are based on the extreme weather conditions shown above. For the heating load the two possible weather conditions are investigated and the worst case is taken as the relevant one.
Apart from the Utilization Factor, the calculation is similar to the heating/cooling demand calculation. The results are based on the extreme weather conditions shown above. For the heating load, two possible weather conditions are investigated and the worst case is taken.
<br style="clear:both" />
<br style="clear:both" />


Zeile 64: Zeile 64:
== Thermal Brigdes ==
== Thermal Brigdes ==
[[Bild:Passive-verification_thermalbridges.png|right|thumb|Thermal bridges]]
[[Bild:Passive-verification_thermalbridges.png|right|thumb|Thermal bridges]]
Summarizes all thermal bridges given in the [[Passive2:Tree_Thermal_Bridges|thermal bridge]] tab of the tree and its heat gains and losses.<br style="clear:both" />
Summarizes all thermal bridges given in the [[Passive2:Tree_Thermal_Bridges|thermal bridge]] tab of the navigation tree. This also displays the heat gains and losses resulting from the thermal bridges.<br style="clear:both" />


== Windows ==
== Windows ==
Zeile 71: Zeile 71:


== Summary Building Envelope ==
== Summary Building Envelope ==
[[Bild:Passive-verification_buildingenvelope.png|right|thumb|Building envelope]]Dimensions of all building elements as well as their U- or Psi-Value. Also the transmission losses of each element, which are also needed for the heat gain/loss statistic are given.<br>
[[Bild:Passive-verification_buildingenvelope.png|right|thumb|Building envelope]] This displays dimensions of all building elements as well as their U- or Psi-Value. It also shows the transmission losses of each element, which are also needed for the balance of heat gains and losses.<br>
The respective final shading effect of each orientation is outlined here as well for both, the heating and cooling period.<br style="clear:both" />
The respective final shading reduction factors for both the heating and cooling periods are shown here, separated by orientation.<br style="clear:both" />


== HVAC Systems ==
== HVAC Systems ==
[[Bild:Passive-verification_hvac.png|right|thumb|HVAC]]
[[Bild:Passive-verification_hvac.png|right|thumb|HVAC]]
An enumeration of all HVAC systems and their influence on the DHW consumption, heat gains/losses and primary energy demand or a equivalenct CO2 emission.<br style="clear:both" />
This table displays an enumeration of all HVAC systems and their influence on the DHW consumption, heat gains/losses and primary energy demand. Also displayed is a value for the equivalent CO2 emissions.<br style="clear:both" />


== Ventilation ==
== Ventilation ==
[[Bild:Passive-verification_ventilation.png|right|thumb|Ventilation]]
[[Bild:Passive-verification_ventilation.png|right|thumb|Ventilation]]
All relevant values related to the mechanical and natural ventilation are displayed here. If there are more than one ventilation units, the total efficency of the ventilation system and the individual ones are listed on bottom. Those numbers also depend on the attached ducts and their instulation standard.
All relevant values for the mechanical and natural ventilation are displayed here. If there is more than one ventilation unit, the total efficiency of the ventilation system as well as the individual units are listed on bottom. Those values also depend on the supply and exhaust duct lengths and their insulation levels.
<br style="clear:both" />
<br style="clear:both" />


== Electricity Demand - Auxiliary Electricity ==
== Electricity Demand - Auxiliary Electricity ==
[[Bild:Passive-verification_auxelectricity.png|right|thumb|Auxiliary electricity]]
[[Bild:Passive-verification_auxelectricity.png|right|thumb|Auxiliary electricity]]
A table containing the energy demand of all HVAC and all affiliated systems. <br style="clear:both" />
A table containing the auxiliary energy demand of all HVAC and affiliated systems. <br style="clear:both" />


== Electricity Demand Of Electric Devices ==
== Electricity Demand Of Electric Devices ==
A list of all input electric devices and their annual electric demand. <br>
A list of all input electric devices and their annual electric demand. <br>
As input of residential and non-residential building differs, WUFI has different graphics for each type.
WUFI has different graphics for residential and non-residential buildings.  


<div class="tleft" style="clear:none">[[Bild:Passive-verification_electricitydemand.png|right|thumb|Residential]]</div>  
<div class="tleft" style="clear:none">[[Bild:Passive-verification_electricitydemand.png|right|thumb|Residential]]</div>  
Zeile 97: Zeile 97:
== Internal Heat Gains ==
== Internal Heat Gains ==
[[Bild:Passive-verification_intheatgains.png|right|thumb|Heat gains]]
[[Bild:Passive-verification_intheatgains.png|right|thumb|Heat gains]]
Internal Heat Gains can either be calculated individually by entering data for home e.g. devices, lighting... or general predefined default values: <br>
Internal Heat Gains can either be calculated by entering project specific data for devices, lighting, etc. or, a general predefined default value may be used. The default values are shown below. <br>
Dwelling: 2.1 W/m²<br>
Dwelling: 2.1 W/m²<br>
Home for elderly/students: 4.1 W/m²<br>
Home for elderly/students: 4.1 W/m²<br>
Zeile 107: Zeile 107:
[[Bild:Passive-verification_dhw.png|right|thumb|DHW]]
[[Bild:Passive-verification_dhw.png|right|thumb|DHW]]
The relevant data for DHW distribution is shown in this section.<br>
The relevant data for DHW distribution is shown in this section.<br>
A list of all distribution pipes and water storages can be found here as well.
A list of all distribution pipes and water storage devices can be found here as well.
<br style="clear:both" />
<br style="clear:both" />

Version vom 30. Mai 2014, 17:50 Uhr

Results of Passive House Verification

This page shows the different sections of the Passive House Verification output report. There will be a short description of the output parameters for each section as well as a screenshot.

Building Information

Building information

The first section summarizes general information about the building itself and important boundary conditions such as the interior temperature and the internal loads.

Passivehouse requirements

Passivehouse requirements

The primary passive house requirements depend mostly on energy demand, mainly in form of cooling and heating as well as primary energy demand. All values are given in a specific value (per square meter/feet) and in total. Heating and cooling demand also provide a peak value(month), which is estimated by the extreme weather conditions in the climate tab.

Secondary Passivehouse Requirements

Secondary requirements

The secondary requirements consist of the HRV efficiency and a percentage chance of overheating of the building. Depending on the likelihood of overheating, WUFI®Passive will give recommendation if a separate cooling system is needed or not.

Building Elements

Building elements

The building elements describes the influences of windows, HVAC systems and electric devices on the energy demand.

Windows

The graphic shows the heat losses and gains of solar radiation through windows separated by orientation. Also average U-values for all windows are given as well as the total glazing area.

HVAC

The energy demand of all HVAC devices is summarized here.

Electricity

The energy demand of all other electric devices is listed here.

Heat Flow

Heat flow

Heat gains and losses are divided into different categories.
Heat gains are separated into solar gains, inner sources, thermal bridges and mechanical heating.

Heat losses are separated into windows & doors, the opaque building envelope, natural ventilation and mechanical ventilation.

Both statistics are displayed in a pie chart.

Climate

Climate

Here you find local climate conditions e.g. the height of the building and ground conditions.
Furthermore there is a graphical overview of the climate given in the localization/climate section and possible calculations of undefined values (e.g. ground/sky temperatures).
The second graph displays the solar radiation separated by orientation.

Calculation Parameters

Calculation parameters

The main boundary conditions for the heat loss calculation are listed here.
Here you will also find the extreme weather conditions for the calculation of the heating/cooling load. For the heating load there are two possible climates available. The relevant climate (the climate with higher calculated heating load) is displayed on bottom.

Annual Heat/Cooling Demand

Heat/Cooling demand

This displays the balance between annual heat gains and losses and thereby calculates the annual heat/cooling demand.
The losses/gains are summarized by categories and their balance is graphically displayed on the bottom.
Note: the heat gains during heating period and the heat losses during the cooling period are reduced by the Utilization Factor. The Utilization Factor is estimated by a complex calculation.

Heating/Cooling Load

Heat/Cooling load

Apart from the Utilization Factor, the calculation is similar to the heating/cooling demand calculation. The results are based on the extreme weather conditions shown above. For the heating load, two possible weather conditions are investigated and the worst case is taken.

Areas

Areas

For each component the most important values are displayed in tabular and graphical form. The results are used for the heating/cooling demand calculation.

Thermal Brigdes

Thermal bridges

Summarizes all thermal bridges given in the thermal bridge tab of the navigation tree. This also displays the heat gains and losses resulting from the thermal bridges.

Windows

Windows

Shows the number, orientation and specific values of all windows and their influence on the heat gains and losses. These results are used in the calculation of the heating and cooling demand.

Summary Building Envelope

Building envelope

This displays dimensions of all building elements as well as their U- or Psi-Value. It also shows the transmission losses of each element, which are also needed for the balance of heat gains and losses.

The respective final shading reduction factors for both the heating and cooling periods are shown here, separated by orientation.

HVAC Systems

HVAC

This table displays an enumeration of all HVAC systems and their influence on the DHW consumption, heat gains/losses and primary energy demand. Also displayed is a value for the equivalent CO2 emissions.

Ventilation

Ventilation

All relevant values for the mechanical and natural ventilation are displayed here. If there is more than one ventilation unit, the total efficiency of the ventilation system as well as the individual units are listed on bottom. Those values also depend on the supply and exhaust duct lengths and their insulation levels.

Electricity Demand - Auxiliary Electricity

Auxiliary electricity

A table containing the auxiliary energy demand of all HVAC and affiliated systems.

Electricity Demand Of Electric Devices

A list of all input electric devices and their annual electric demand.
WUFI has different graphics for residential and non-residential buildings.

Residential
Non-residential


Internal Heat Gains

Heat gains

Internal Heat Gains can either be calculated by entering project specific data for devices, lighting, etc. or, a general predefined default value may be used. The default values are shown below.
Dwelling: 2.1 W/m²
Home for elderly/students: 4.1 W/m²
Office/administrative building: 3.5 W/m²
Schools: 2.8 W/m²

DHW and Distribution

DHW

The relevant data for DHW distribution is shown in this section.
A list of all distribution pipes and water storage devices can be found here as well.